Demand Charge Guide
Demand charges are based on your highest average power demand in a month, not on total energy consumed. This guide explains how peaks occur, how they are metered and how battery storage effectively cuts them.
5 min read · updated 2026-10-14
At a glance
What you need to know
- Demand charges track monthly peak power – a single spike can drive up the entire monthly bill
- The peak is typically measured over a 15-minute rolling window
- The battery does not need to cover the entire peak: even partial shaving lowers the charge
- Identifying the source of demand spikes is essential before sizing the battery
How demand charges are calculated
Under capacity-based distribution tariffs, the distribution system operator bills based on the highest average power recorded during the month, typically measured in 15-minute intervals. Total energy consumed plays no role here: two sites with identical monthly consumption can have drastically different bills depending on how sharply their load peaks.
Tariff sheets from distribution operators show typical rates: the tariffs we analysed feature a demand-based charge ranging from €1.37 to €5.97/month/kW. For example, for a 100 kW peak, the monthly charge ranges from €137 to €597, and for a 300 kW peak, from €411 to €1,791.
Many commercial tariffs also include a fixed standing charge and a volumetric distribution fee per kWh, making the demand charge just one component of the bill. Electricity tax is either 2.325 c/kWh (Class 1) or 0.135 c/kWh (Class 2), excluding VAT.
What causes power peaks
The most common sources of peaks are machine and motor start-ups, simultaneous starts of compressors and cooling equipment, switching on heating elements, air conditioning, and loads accumulating in the morning and afternoon. The balance between solar generation and consumption can also create a peak if the property draws power from the grid precisely when generation is at its lowest.
Before sizing a battery, it is essential to examine actual metering data: when the peak occurs, how long it lasts, and whether it recurs daily. According to Motiva's recommendation, an industrial energy audit is this first step.
How a battery shaves peaks
The battery monitors the site's power demand and discharges into consumption when the load exceeds a set threshold. When the limit is set at, for example, 80% of the measured peak, the battery covers the excess. As a result, the month's measured peak does not exceed the threshold, and the demand charge is determined by the lower value.
In practice, the battery does not need enough power to cover the entire peak. A smaller battery reduces the peak correspondingly less, but the investment is lower. The battery's capacity determines how long a peak it can sustain: the longer the peak, the more stored energy is required.
Example calculation
Consider a site with a measured monthly peak of 250 kW. If the battery's power output is 100 kW and it covers the excess, the monthly peak remains at 150 kW.
The reduction in demand charges is 137–597 euros per month, or 1 644–7 164 euros per year, when the entire monthly peak can be shaved.
The figures are based on power-based tariff lists from distribution grid operators (Caruna Oy, Caruna Espoo Oy, Elenia) and are VAT 0% values. Actual savings depend on whether the peak recurs every month and what proportion of it the battery manages to cover.
In addition to demand charges, the battery can deliver savings on the consumption component of distribution tariffs and spot electricity price differentials. These should be calculated separately, as their predictability varies.
Checks and limitations
Peak shaving does not work if the peak is very brief, sporadic, or occurs when the battery is depleted. This is why battery sizing is based on measured load profiles, not estimates. In addition, it must be ensured that the battery does not create a new peak while charging: charging is typically scheduled outside peak load hours.
Electricity tax classification should be verified separately. Tax Class 2 has strict eligibility criteria and is only granted for specific applications, so calculations should not rely on it without confirmation.
Read more
Full guide as a PDF
The summary gives you an overview, but system sizing is based on your site's details. Download the full guide and use it as a starting point for a discussion with us.
Models used in the example calculations
- Emaldo PL-EL-100/209100 kW · 209 kWh
- Emaldo PL-EL-125/261125 kW · 261 kWh
Frequently asked questions
Questions about this guide's topic
How large a battery is needed to cut demand charges?
The battery's power output is determined by how much of the peak you want to shave, and its capacity by how long the peak lasts. Our smallest commercial model is 100 kW / 209 kWh, and the largest is 400 kW / 836 kWh.
Does the battery also cut demand charges when the peak is sporadic?
Only partially. If a peak occurs rarely, the battery will shave it, but the monthly peak might arise at some other moment. For this reason, metering data should always be reviewed before making a decision.
Can a battery also increase the demand charge?
Yes, if it charges at the wrong time. The charging schedule is configured so that the battery does not increase the monthly peak, and this is verified during commissioning.
Sources and updates
Content reviewed 2026-10-14. Example calculations are indicative: tariffs, reserve market prices and technical suitability are always checked for each site.